GEODONICS
by John Siegenthaler, P.E.
November 1, 2009
The marriage between geothermal heat pumps and hydronics offers profitable opportunities.
In the mid 1980s, the first serious market for
geothermal heat pump systems sprang to life in the U.S. As was the case with
floor heating, the availability of a highly reliable high-density polyethylene
piping system instilled confidence that geothermal systems could operate
without leaks in buried piping that would be very difficult and expensive to
fix. This assurance allowed the market to gain momentum. And this was all
before words like “green” and “sustainable” became engrained in the global
mindset.
Today, the geothermal heat pump market is thriving in the U.S. and abroad. It’s
driven by reliable technology, the ability to provide both heating and cooling,
and a potential “amplifying” load for electricity produced from renewable
sources such as solar photovoltaics, hydropower and combined heat/power
systems. The recent enactment of a 30% uncapped federal tax credit for residential systems makes
this technology a very appealing option.
Although the majority of residential and light commercial geothermal heat pump
systems use water-to-air heat pumps with forced air delivery, there are many
unique and profitable opportunities for combining geothermal heat pumps with
hydronics.
The type of geothermal unit used for supplying
hydronic systems is called a water-to-water heat pump. It absorbs heat from a
stream of low temperature water (or mix of water and antifreeze), increases the
temperature of that heat using a standard vapor compression cycle, then
delivers the higher temperature heat to another stream of water. A simplified
concept is shown in Figure 1.
The source of the low temperature heat could be ground water from a lake, large
pond or well. Systems that circulate ground water directly through the heat
pump are called open loop
systems. They have been used successfully provided there is an ample source of
ground water, and that the quality of that water is such that it will not
corrode or scale the heat pump’s internal heat exchanger.
The other option is a closed
loop system. Here the water or mixture of water and antifreeze is
completely contained in a buried piping system that operates under slight
pressure. This fluid in the buried earth loop never directly contacts the soil,
and should remain in the loop for decades.
The chemistry of a closed loop system is far easier to control than the
condition of ground water at a given site. Thus, closed loop systems are
generally preferable from the standpoint of long system life with low
maintenance.
The Lower The Better
|
|
Figure 2. Source: ClimateMaster Corp. |
|
One of the most important aspects of merging a
ground source heat pump to a hydronic distribution system is the required
supply water temperature of the latter. The lower the water temperature
requirement of the distribution system, the higher the heat pump’s
efficiency.
Examples of low water temperature hydronic distribution systems include slab
type radiant floors with low resistance coverings (or no coverings). Properly designed radiant wall and ceiling
panels are another possibility, as are generously sized panel radiators. My suggestion is to draw the line at a supply
water temperature no higher than 120°F under design load conditions. Although
some heat pumps are capable of higher temperatures, their efficiency drops off
significantly as the water temperature they are asked to supply increases above
120°F.
Heat emitters, such as fin-tube baseboard or plateless staple-up radiant
tubing, are not suitable for use with geothermal heat pumps. The supply water
temperature of such systems is often based on the use of water supplied from a
boiler in the temperature range of 170-200°F. This is well beyond what any
currently available geothermal heat pump can supply. Adding enough baseboard length or bringing
staple-up tubing closer together is just not practical (think almost four times
more baseboard that would be installed in a typical system).
Buffering the Load
A significant benefit of hydronics is the
ability to easily divide a distribution system into zones. Retaining this
benefit when the heat source is a geothermal heat pump requires a buffer tank.
The water within this insulated tank separates the rate of heat production by
the heat pump from the rate of heat dissipation by the distribution system.
This is necessary because most current generation water-to-water heat pumps are
on/off devices with very little internal thermal mass. Unlike cast-iron boilers, they are highly
“flow sensitive.” While operating, they must have a steady flow of fluid on
both their source and load sides. The load side is usually where issues
arise. Reduced flow due to inactive zone
circuits will cause the heat pump to shut off to protect itself from
potentially dangerous internal pressures or temperatures. The schematic in Figure
2 shows an example of a water-to-water geothermal heat pump supplying
a zoned heating system.
In this system, the water-to-water heat pump is turned on and off by an outdoor
reset controller — the same type of controller that you probably already sell
to control boilers. This controller
calculates the necessary water temperature in the buffer tank based on outdoor
temperature. As the outdoor temperature increases, this controller reduces the
average temperature of the buffer tank and vice versa. The controller then
turns the heat pump on and off as necessary to keep the buffer tank temperature
close to this calculated target temperature. This action maximizes the
efficiency of the heat pump and eliminates the need for any type of mixing
device between the heat source and the load.
Domestic water is heated by a “desuperheater”
heat exchanger within the heat pump.
This desuperheater is heated by hot refrigerant directly from the
compressor discharge. It transfers this
heat to a stream of domestic water passing through the other side of the heat
exchanger. This steam carries the heat to a conventional electric water
heater. The electric element only
operates as necessary to “top off” the temperature within the storage tank.
Many geothermal heat pumps, including water-to-water units, can be ordered with
this desuperheater. When this option is ordered, the heat pump usually includes
a small bronze internal circulator to convey water between the desuperheater
and tank.
Notice that the distribution system uses a variable speed pressure regulated
circulator in combination with zone valves. This is just one example of how the
latest hydronics hardware dovetails well with geothermal heat pumps.
Cool It
|
|
Figure 5. Source: ClimateMaster Corp. |
|
Most water-to-water heat pumps can be ordered as
“reversible” units. As such they come equipped with an electrically operated
refrigerant reversing valve. When powered, this valve effectively swaps the
function of the evaporator and condenser as shown in Figure 3.
Chilled water is now produced on the load side of the heat pump, while the
earth loop serves as the heat sink.
Water in the range of 40-50°F is ideal for cooling with chilled water air
handlers. Some systems may use a single air handler that’s matched to the
cooling output of the heat pump. However, just as hydronic heating can be
zoned, so can hydronic cooling. Multiple
chilled water air handlers can be supplied from a single chilled water buffer
tank. Smaller units, such as those shown in Figure 4, can be
piped with 5/8-inch or 3/4-inch PEX or PEX-AL-PEX tubing wrapped with
vapor-resistant insulation to prevent condensation. Each air handler can be
equipped with a zone valve. These zones can then be supplied by a single
variable speed, pressure regulated circulator — just like that used for the
heating zones. A schematic showing the concept is given in Figure 5.
Beyond these basic designs are dozens of other possibilities. For example,
larger systems can use multiple water-to-water heat pumps operated in stages.
These heat pumps can be controlled by a multi-stage boiler controller, just
like those used for multiple boilers.
Systems can also be constructed using two buffer tanks: One for warm water and
the other for chilled water. This approach is well suited for buildings where
fall and spring mornings require heating, but increasing temperatures or
increasing internal gains require cooling by afternoon. In some systems it’s
even possible to use a water-to-water heat pump to simultaneously create both
warm and chilled water in the two buffer tanks.
If you already sell state-of-the-art hydronics hardware for use in boiler-based
systems, expanding into water-to-water based geothermal heat pumps is a
natural. You probably already know much of the hydronics technology that holds
a typical geothermal heat pump system together. As customers increasingly seek
“green” solutions to heating and cooling, having the expertise to facilitate a
“geodonic” system is a profitable opportunity.
|