Static Pressure Meters
by Jim Wheeler
August 1, 2010
Most residential systems don’t move enough air.
One
of the most-needed and least-owned HVACR test instruments is one that reads air
handler static pressures. The fact is, most residential and many commercial
HVACR systems that rely on interior air motion are either undersized or have
clogged components, and most technicians carry nothing at all to diagnose the
problem!
It’s as simple as this: If the pressure across an air handler or furnace (as
read from the return to the discharge) is higher than specified, it isn’t
circulating enough air, so it’s losing efficiency and the evaporator coil is in
danger of freezing, or the furnace is in danger of overheating. Also, if the
air pressure across an evaporator coil exceeds its specification limits, it is
clogged and needs to be cleaned. However, if that coil is an internal part of
the air handler, the air handler output pressures will be low. This isn’t brain
surgery, just common sense!
Did I say that most residential systems don’t move enough air? Yes, in my
experience this is true. The maximum design static pressure across most
residential air handlers is .5-inch of water column (wg). Yet I know many
contractors who design all their discharge ductwork (forgetting what’s
happening at the return) at 1-inch, which puts the resulting air flow well
under proper design minimums!
Then there are other factors that enter the picture, such as closed discharge
grilles, the common use of high-static-pressure air filters (such as
electrostatic filters), undersized returns, rooms with closed doors that have
no returns, and most of all, dirty evaporator (indoor) coils. However, air
handlers should also be checked to ensure that their blowers are clean, working
properly, and set at the correct speed.
Do you know how most HVACR service technicians diagnose and find such problems?
They usually start out by taking refrigerant pressure readings. If they find
low refrigerant pressures, they commonly add refrigerant to bring the pressures
up, grossly overcharging the system. When this doesn’t work, they check the air
filters, then they start tearing things open to visually find the problem —
which takes a long time and usually does some damage along the way.
However, there are simple, inexpensive service tools to quickly diagnose these
problems: static pressure gauges. I really like Dwyer’s Model 460 Air Meter
(it’s the one I’ve used for years). It’s small, easy to use, and quite
inexpensive. So I suggest that you look into stocking them, but then you may
have to provide training classes to show technicians how to use them and how to
diagnose problems from the readings.
The problem with some static-pressure gauges is that they can be quite
expensive, they are often unwieldy, and some employ a special liquid that leaks
out. However, the Dwyer air gauge uses no oil, it doesn’t have to be dead level
to work well, and it can also be employed to check air
velocities.
To use a static-pressure gauge, you simply drill a 1/4-inch hole in the
entering and leaving ducts. Then connect the included rubber hose from the hole
in the duct discharge to the input side of the gauge — on the Model 460 you
hold your thumb over the output side of the gauge to put it into the proper
range — and take a reading. Then connect the hose from the hole in the return
duct to the gauge output side to get a negative-pressure reading. Thereafter,
you add the static pressure from the negative to the positive to obtain the
total static pressure reading (-.1 inch wg to +.4 inch wg = .5 inch wg). And
finally, using metallic tape, seal the holes that you drilled.
|